Read nodes' heat and power: GPUs, CPUs, board inlet, RAPL
Every agent samples, at most every ten seconds: nvidia-smi's temperature, HBM temperature, power draw, enforced limit and throttle reasons per GPU; hwmon's CPU package and board inlet temperatures; and CPU package power from RAPL's energy counters. Sent with heartbeats, published as metrics and shown on the node page; unmeasured sensors are absent, never zero. Observe-only, step 0 of docs/facility-aware-placement.md, which now describes the agent source and what these readings can and cannot say. Co-Authored-By: Claude Opus 5.5 (1M context) <noreply@anthropic.com>
This commit is contained in:
1 parent
8724dc027a
commit
cd10e086c8
15 files changed
+996
-172
No files matched your search
@@ -1,9 +1,11 @@
|
||||
# Facility-aware placement: rack power, temperature and cooling
|
||||
|
||||
**Status: planned, not built.** This is the design for step 5 of resource
|
||||
allocation, after reserved CPU cores and memory (1), capacity classes and
|
||||
preemption (2), tenant capacity quotas (3) and sizing by measured throughput
|
||||
(4), all of which shipped in v0.10.5. Nothing here exists in the code yet.
|
||||
**Status: planned; its first step, reading the nodes' own sensors, is built.**
|
||||
This is the design for step 5 of resource allocation, after reserved CPU cores
|
||||
and memory (1), capacity classes and preemption (2), tenant capacity quotas (3)
|
||||
and sizing by measured throughput (4), all of which shipped in v0.10.5. Of
|
||||
what follows, only the node sensors (rollout step 0) exist in the code: they
|
||||
are read, published and shown, and change no decision.
|
||||
|
||||
## Why
|
||||
|
||||
@@ -35,7 +37,7 @@ and never let missing data stop the cluster.
|
||||
| Headroom: the scheduler dry-run on a copy of the inventory | Room that respects power budgets, for free |
|
||||
| Preemption with classes, minimums and a dry run (step 2) | Shedding load from a hot rack in the right order |
|
||||
| Measured throughput per profile (step 4) | Tokens per watt as a placement preference |
|
||||
| GPU temperature from NVML, per card | A node-level thermal signal that needs no facility data |
|
||||
| Node sensors, read by every agent (step 0, built) | Heat and power with no facility integration: see below |
|
||||
| `internal/promq`, a Prometheus client | Reading facility metrics that DCIM exporters publish |
|
||||
|
||||
## Concepts
|
||||
@@ -116,8 +118,8 @@ starts nor ends anything:
|
||||
| Condition | Enters when | Placement |
|
||||
|---|---|---|
|
||||
| `ok` | below the warm threshold for 5 min | normal |
|
||||
| `warm` | inlet above the warm threshold for 2 min, or GPU temperatures near throttling | allowed, scored down: other domains first |
|
||||
| `hot` | inlet above the hot threshold for 2 min, or a cooling unit in alarm | no new placements, as a cordon would, but automatic and reversible |
|
||||
| `warm` | inlet above the warm threshold for 2 min, GPU temperatures near throttling, or any GPU thermally throttled | allowed, scored down: other domains first |
|
||||
| `hot` | inlet above the hot threshold for 2 min, a cooling unit in alarm, or a sustained share of the domain's GPUs thermally throttled | no new placements, as a cordon would, but automatic and reversible |
|
||||
| `unknown` | no fresh reading | as `ok`, and reported as unknown |
|
||||
|
||||
**Shedding** (optional, off by default): a domain `hot` for longer than its
|
||||
@@ -186,9 +188,39 @@ type FacilitySource interface {
|
||||
query: max by (row) (crac_alarm)
|
||||
domain_label: row
|
||||
```
|
||||
- **Agents.** What the nodes can read themselves: GPU power and temperature from
|
||||
NVML, node power from Redfish or IPMI where the BMC allows it. Needs no
|
||||
facility integration, and gives node-level signals on day one.
|
||||
- **Agents (built, step 0).** What each node reads about itself, every ten
|
||||
seconds at most, sent with its heartbeat:
|
||||
- **GPUs, from nvidia-smi:** temperature, memory (HBM) temperature where the
|
||||
driver reports it, power draw, the enforced power limit, and what is
|
||||
holding the clocks down now — `sw_power_cap`, `hw_slowdown`, `sw_thermal`,
|
||||
`hw_thermal`, `power_brake`.
|
||||
- **CPUs, from hwmon** (what lm_sensors reads, without it installed): the
|
||||
package temperature, or the hottest core; and the board's inlet or ambient
|
||||
sensor where it has one (`SYSTIN`, `Inlet`, `Ambient`).
|
||||
- **CPU power, from RAPL:** the packages' energy counters over time,
|
||||
subdomains not counted twice, counter wrap handled.
|
||||
|
||||
A machine without a sensor reports nothing for it, never a zero; a VM has
|
||||
none of them. Published as `llmgw_gpu_temperature_celsius`,
|
||||
`llmgw_gpu_memory_temperature_celsius`, `llmgw_gpu_power_watts`,
|
||||
`llmgw_gpu_power_limit_watts`, `llmgw_gpu_throttled{reason}`,
|
||||
`llmgw_node_cpu_temperature_celsius`, `llmgw_node_cpu_power_watts` and
|
||||
`llmgw_node_inlet_temperature_celsius`, and on each node's page.
|
||||
|
||||
What they can and cannot say:
|
||||
- **Throttling is the strongest signal there is.** A temperature is a proxy;
|
||||
a card holding its clocks down is the fact that invalidates its measured
|
||||
capacity, and it needs no threshold to be chosen.
|
||||
- **Measured power** is GPU draw plus CPU packages; memory, disks, fans and
|
||||
power-supply losses are not in it, so a node's draw is that plus an
|
||||
estimated remainder. A rack's is its llmgw nodes' plus a declared figure
|
||||
for everything else in it: switches and storage report nothing here.
|
||||
- **CPU and GPU temperatures follow the load, not the room.** A hot rack is
|
||||
inferred from many nodes running hot at comparable load, or from
|
||||
throttling, not from one node's CPU. Only a board inlet sensor reads the
|
||||
air, and most boards have none.
|
||||
- **No budget comes from a sensor.** A reading is a draw; the cap it is
|
||||
measured against still comes from the facility.
|
||||
- **Simulated.** Readings from a script, for tests and for rehearsing a
|
||||
thermal event on a cluster without facility data.
|
||||
|
||||
@@ -223,14 +255,17 @@ type FacilitySource interface {
|
||||
|
||||
Each step ships on its own and is useful without the next:
|
||||
|
||||
0. **Node sensors, observe-only (built).** GPU heat, power and throttling,
|
||||
CPU heat and power, inlet air where the board has a sensor; published and
|
||||
shown, no decision changed.
|
||||
1. **Location and spreading.** Well-known labels, domains from labels, replicas
|
||||
spread across racks and PDUs, locations on the node views. No facility data
|
||||
needed.
|
||||
2. **Power budgets from a static file.** Caps and margins, estimated draw per
|
||||
replica (declared or derived), hard limit in placement and headroom.
|
||||
3. **Readings, observe-only.** The Prometheus and agent sources, conditions
|
||||
with hysteresis, measured power folded into headroom; decisions shown, not
|
||||
enforced.
|
||||
3. **Readings, observe-only.** The Prometheus source beside the agents',
|
||||
conditions with hysteresis (throttling first among them), measured power
|
||||
folded into headroom; decisions shown, not enforced.
|
||||
4. **Thermal enforcement.** `warm` scored down, `hot` refused, manual hold and
|
||||
release.
|
||||
5. **Shedding and tokens per watt.** Opt-in shedding through step 2's
|
||||
|
||||